| 2002-09-12 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM INSTALLATION. |
| | THE FIRE ALARM SYSTEM SHALL BE CLASS A |
| | OR FULLY ADDRESSABLE. |
| | |
| | 2) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER SYSTEM INSTALLATION. |
| | THE HYDRAULIC CALCULATIONS LISTS |
| | PALM BEACH COUNTY FIRE RESCUE AS THE |
| | AHJ. IT SHOULD READ WEST PALM BEACH |
| | FIRE RESCUE. HOW DOES THE BACKFLOW |
| | DEVICE AND FIRE DEPARTMENT CONNECTION |
| | DO NOT INTERFERE WITH EXITING FROM |
| | THE STAIRTOWER. |
| | |
| | 3) IF FUTURE SECURITY DEVICES ARE |
| | INSTALLED FOR THE GARAGE HOW IS EXITING |
| | GOING TO BE ACCOMPLISHED. |
| | |
| | 4) ELECTRONIC SWITCHES WILL BE REQUIRED |
| | ON BACKFLOW DEVICE. SEE CIVIL DRAWING |
| | DETAILS. |
| | |
| | 5) DOORS # 9 SHALL BE AT LEAST 1 1/2 |
| | RATED SINCE A TWO HOUR FIRE SEPARATION |
| | IS REQUIRED BETWEEN THE GARAGE AND |
| | OTHER PORTIONS OF THE BUILDING. |
| | |
| | 6) AN EMERGENCY LIGHT FIXTURE IS |
| | LOCATED OUTSIDE OF THE STAIRTOWER ON |
| | PAGE E-1. |
| | |
| | 7) EXITS ARE TAKING PERSONS INTO A |
| | MORE HAZARDOUS AREA THE GARAGE FROM |
| | THE INTERIOR TENANT SPACES. |
| | |
| | 8) PLEASE INDICATE EXHAUST AIR CFM'S |
| | FOR PARKING GARAGE MECHANICAL |
| | VENTILATION. |
| | |