| 2002-09-18 00:00:00 | ******************** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | THAT MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | 2)NOTE: PLEASE NOTE CIRCUITING NEEDS TO |
| | BE SHOWN FOR ALL BRANCH CIRCUITS ON |
| | PLANS. |
| | |
| | 3)NOTE: PLEASE NOTE EM LTS/EXITS LTS TO |
| | BE ON SAME AREA BRANCH CIRCUITS. PLEASE |
| | SEE 700-12 NEC. |
| | |
| | 4)NOTE: PLEASE CLARIFY EM LT BEING SHOWN |
| | TIED INTO TELEPHONE LINE.? (SECOND FLOOR |
| | |
| | 5)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON PLANS. |
| | |
| | 6)NOTE: PLEASE CLARIFY/LABEL PANEL SHOWN |
| | ON E-2 LAUNDRY AREA? |
| | |
| | 7)NOTE: IT WAS NOTED THAT A 3/4" CONDUIT |
| | STUB UP FOR TELE. PLEASE NOTE AND NOTE |
| | ON PLANS THAT ALL LOW IS REQ`D TO BE |
| | PERMITTED, INSTALLED AND INSPECTED |
| | BEFORE CEILING IS INSTALLED. |
| | PLEASE NOTE, IF NOT INSTALLED BEFORE |
| | ROUGH, CONDUIT SHALL BE COMPLETE TO |
| | TELEPHONE ROOMS. |
| | |
| | 8)NOTE: PLEASE NOTE CIRCUITS ARE BEING |
| | LABELED AS 1-POLE ON PLANS, AS 2-POLE |
| | ON PANEL SCHEDULES AND YET ONLY TAKING |
| | ONE SPACE ON PANEL?? PLEASE CORRELATE. |
| | |
| | 9)NOTE: PLEASE NOTE REQ`MENTS FOR FAIR |
| | HOUSING. PLEASE SEE FHAR 24 CFR 100.205 |
| | DEVICE HEIGHTS/FHA MUST BE NOTED ON PLAN |
| | |
| | 10)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| | KITCHEN COUNTERSPACE. PER 210-52-C-1. |
| | MISSING A FEW. |
| | |
| | 11)NOTE: PLEASE NOTE A UNIT "H" BEING |
| | SHOWN ON PLANS AND NO LAYOUT SUBMITTED. |
| | PLEASE ALSO NOTE A LAYOUT FOR A UNIT "G" |
| | ? PLEASE SUBMIT/ CORRELATE. |
| | |
| | 12)NOTE: PLEASE SUBMIT ALL PANEL SCHEDU- |
| | -LES. |
| | PLEASE ALSO NOTE PANELS ARE BEING SHOWN |
| | AS 24 CIR AND 30 CIR? PLEASE SEE |
| | PREVIOUS COMMENT ABOUT CIRCUITING NOT |
| | CORRELATING. |
| | |
| | 13)NOTE: PLEASE NOTE SD`S ARE INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS. PLEASE NOTE |
| | ROOMS W/ CLOSETS AND/OR BATHS ARE CON- |
| | -SIDERED SLEEPING ROOMS. NFPA-72 2-2.1.1 |
| | .1. |
| | |
| | 14)NOTE: ALL LOAD CALCULATIONS ARE REQ`D |
| | TO BE SHOWN. PLEASE NOTE ALL CONTINUOUS |
| | LOADS AT 125%. PLEASE SEE 220-3,220-10, |
| | 220-11,220-13, 230-42, 215-3,, ETC. |
| | |
| | 15)NOTE: PLEASE SHOW LOCATIONS OF A/C |
| | COND UNITS ON ELECTRICAL PLANS. ROOF TOP |
| | ?? PLEASE NOTE DISC`S PER 440-11 AND |
| | GFI PER 210-63. |
| | |
| | 16)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | CIRCUITS FOR BEDROOM RECEPTS PER 210-12. |
| | |
| | 17)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW MAINS/PANELS/ BRKRS PER 110-9, |
| | 215-5. |
| | |
| | 18)NOTE: PLEASE NOTE, E-5 NOTES ALL |
| | WIRING TO BE MIN #12 AND PANEL SCHEDULE |
| | SHOWS #14 ON SOME? PLEASE CORRELATE OR |
| | NOTE ,, . |
| | |
| | 19)NOTE: PLEASE SHOW LOCATION OF SERVICE |
| | PLEASE NOTE GROUPING OF MAINS PER 230-72 |
| | IT IS NOTED TWO SEPARATE SERVICES ARE |
| | SHOWN ON RISER DIAGRAM. PLEASE NOTE |
| | THAT A SECOND SERVICE IS NOT PERMITTED |
| | PER 230-2. |
| | |
| | PLEASE NOTE THAT THERE MAY BE OTHER |
| | COMMENTS DUE TO CHANGES IN PLANS. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |