| Plan Review Notes For Permit 02090280 |
| Permit Number |
02090280 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-25 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE TOTAL LOAD SHOWN AT | | | 1238.51 AMPS. | | | PLEASE SEE 60A SUB PANEL, SHOWN AS 65A. | | | | | | PLEASE CORRELATE PANELS AND REVISE LOAD | | | CALCS. | | | | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW, IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|