| Plan Review Notes For Permit 02090252 |
| Permit Number |
02090252 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-03-27 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE NOTE, ALL PLANS DRAWN | | | BY AN ARCHITECT/ENGINEER CONTAIN- | | | -ING A TITLE BLOCK: MUST BE SIGNED, | | | DATED AND SEALED BY THAT ARCH/ENG. | | | PER FS 481.221 471.025 | | | FAC 61G15-23.002, 61G1-16.004 | | | | | | 2} PLEASE CLOUD, TRIANGLE , HIGHLIGHT, | | | OR INDICATE IN SOME MANNER(EXPLAINED ON | | | REVISION SUBMITTAL FORM) THE CHANGES TO | | | THE PLANS. | | | | | | 3} PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECT--ED PER 210.8A-6 | | | | | | 4} PLEASE SEE RECEPTS SERVING | | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | | SEC'S 1,2,3,4 AND 5 | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|