| Plan Review Notes For Permit 02090252 |
| Permit Number |
02090252 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-16 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 2} ANY LOW VOLTAGE WIRING TO BE | | | INSTALLED MUST BE SHOWN ON A PLAN AND | | | PERMITTED.IF LOW VOLTAGE SYSTEMS ARE TO | | | BE PART OF THIS APPLICATION,ALL OUTLETS | | | HAVE TO BE SHOWN ON THIS PLAN. | | | | | | 3} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.THE ONE SHOWN ON | | | THE PANEL SCHEDULE MUST BE FOR THE | | | EXISTING BATH AS ONLY 2-15 AMP CIRCUITS | | | ARE SHOWN AS BEING ADDED FOR THE ENTIRE | | | ADDITION. PLEASE CLARIFY. | | | | | | 4} PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 5} PLEASE NOTE FRONT AND REAR | | | RECEPTS REQ`D PER 210-52E | | | | | | 6} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|