Plan Review Notes
Plan Review Notes For Permit 02090252
Permit Number 02090252
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-16 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 2} ANY LOW VOLTAGE WIRING TO BE
 INSTALLED MUST BE SHOWN ON A PLAN AND
 PERMITTED.IF LOW VOLTAGE SYSTEMS ARE TO
 BE PART OF THIS APPLICATION,ALL OUTLETS
 HAVE TO BE SHOWN ON THIS PLAN.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.THE ONE SHOWN ON
 THE PANEL SCHEDULE MUST BE FOR THE
 EXISTING BATH AS ONLY 2-15 AMP CIRCUITS
 ARE SHOWN AS BEING ADDED FOR THE ENTIRE
 ADDITION. PLEASE CLARIFY.
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 6} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392