Plan Review Notes
Plan Review Notes For Permit 02090252
Permit Number 02090252
Review Stop B
Sequence Number 1
Notes
Date Text
2002-09-30 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02090252
 ADD: 230 WRENA DR
 CONT: O/B STILLS, JAMES
 TEL: (561)615-9101
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE DESIGN CERTIFICATION FORM USED
 WAS FOR THE SBC 1997 CODE. THIS FORM IS
 NO LONGER IN USE AS OF NEW STATE LAW
 REQUIRING THIS INFORMATION TO BE ON THE
 DRAWINGS THEMSELVES.
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 2)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) EXTERIOR SWING DOOR, SINGLE/ DOUBLE
 B) MULLIONS
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 4)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
  
 5) 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 6)1606.1.1 EXC (4) AF&PA WOOD FRAME
 CONSTRUCTION MANUAL FOR ONE & TWO
 FAMILY - 1995 SBC HIGH WIND EDITION
 1996 SHALL BE PERMITTED FOR APPLICABLE
 WOOD FRAME BUILDINGS OF GROUP 3 OCCU-
 PANCY FOR A BABIC WIND SPEED OF 146 MPH
 OR LESS IN EXPOSURE B AND 124MPH OR LESS
 IN EXPOSURE C IN ACCORDANCE WITH FIGURE
 1606 AND SECTION 1606.1.8.
  
 7)905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 8)905.2.1 RESIENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1(B) ALL SMOKE DETECTORS
 SPECIFIED IN A-8-1.2.1(A) FOR EXISTING
 CONSTRUCTION ARE REQUIRED, AND, IN ADD-
 TION, A SMOKE DETECTOR IS REQUIRED IN
 EACH SLEEPING ROOM.
  
 9) TABLE 2306.1 PALM BEACH COUNTY
 AMENDMENTS
 ROOF SHEATHING NAILING REQUIREMENTS
  
 ZONE 1 & 28D COMMON
 6" EDGES & 6" INTERMEDIATES
  
 ZONE 38DCOMMON
 4" EDGES & 6" INTERMEDIATES
  
 10)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36".
  
 11)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 MASTER BATH,
  
 12)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026