| 2002-09-30 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02090252 |
| | ADD: 230 WRENA DR |
| | CONT: O/B STILLS, JAMES |
| | TEL: (561)615-9101 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) THE DESIGN CERTIFICATION FORM USED |
| | WAS FOR THE SBC 1997 CODE. THIS FORM IS |
| | NO LONGER IN USE AS OF NEW STATE LAW |
| | REQUIRING THIS INFORMATION TO BE ON THE |
| | DRAWINGS THEMSELVES. |
| | FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | FIGURE 1606 WIND-BORNE DEBRIS |
| | REGION; INDICATES THAT W.P.B. CITY OF IS |
| | LOCATED IN THE 140 MPH ZONE. PLANS ARE |
| | TO INDICATE THIS. |
| | |
| | 2)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | |
| | 3) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED.MISSING REPORTS: |
| | A) EXTERIOR SWING DOOR, SINGLE/ DOUBLE |
| | B) MULLIONS |
| | 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 4)1707.4.4.1 ANCHOR REQUIREMENTS: |
| | WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| | ED IN ACCORDANCE WITH THE PUBLISHED |
| | MANUFACTURER'S RECOMMENDATIONS TO |
| | ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| | SUBSTITUTE ANCHORING SYSTEM USED FOR |
| | THE SUBSTRATE NOT SPECIFIED BY THE |
| | FENESTRATION MANUFACTURER SHALL PROVIDE |
| | EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| | TED BY ACCEPTED ENGINEERING PRACTICES. |
| | |
| | |
| | 5) 1707.3.1 JOIST HANGERS, FRAMING |
| | ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| | ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| | LABELED AND LISTED FOR THEIR LOAD CARRY- |
| | ING CAPACITY. |
| | |
| | 6)1606.1.1 EXC (4) AF&PA WOOD FRAME |
| | CONSTRUCTION MANUAL FOR ONE & TWO |
| | FAMILY - 1995 SBC HIGH WIND EDITION |
| | 1996 SHALL BE PERMITTED FOR APPLICABLE |
| | WOOD FRAME BUILDINGS OF GROUP 3 OCCU- |
| | PANCY FOR A BABIC WIND SPEED OF 146 MPH |
| | OR LESS IN EXPOSURE B AND 124MPH OR LESS |
| | IN EXPOSURE C IN ACCORDANCE WITH FIGURE |
| | 1606 AND SECTION 1606.1.8. |
| | |
| | 7)905.2.1 APPROVED SINGLE-STATION OR |
| | MULTIPLE STATION SMOKE DETECTORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| | CHAPTER 2, WITHIN EVERY DWELLING UNIT |
| | WITHIN AN APARTMENT HOUSE, CONDOMINIMUM, |
| | OR TOWNHOUSE AND EVERY GUEST OR SLEEPING |
| | ROOM IN A MOTEL, HOTEL, OR DORMITORY & |
| | SLEEPING ROOMS IN RESIDENTIAL CARE/ |
| | ASSISTED LIVING OCCUPANCIES. WHERE MORE |
| | THAN ONE DETECTOR IS REQUIRED TO BE |
| | INSTALLED WITHIN INDIVIDUAL DWELLING |
| | UNIT, THE DETECTOR SHALL BE WIRED IN |
| | SUCH A MANNER THAT THE ACTUATION OF ONE |
| | ALARM WILL ACTIVATE ALL THE ALARMS IN |
| | THE INDIVIDUAL UNIT. |
| | |
| | 8)905.2.1 RESIENTIAL SMOKE ALARMS: |
| | NFPA 72.A-8-1.2.1(B) ALL SMOKE DETECTORS |
| | SPECIFIED IN A-8-1.2.1(A) FOR EXISTING |
| | CONSTRUCTION ARE REQUIRED, AND, IN ADD- |
| | TION, A SMOKE DETECTOR IS REQUIRED IN |
| | EACH SLEEPING ROOM. |
| | |
| | 9) TABLE 2306.1 PALM BEACH COUNTY |
| | AMENDMENTS |
| | ROOF SHEATHING NAILING REQUIREMENTS |
| | |
| | ZONE 1 & 28D COMMON |
| | 6" EDGES & 6" INTERMEDIATES |
| | |
| | ZONE 38DCOMMON |
| | 4" EDGES & 6" INTERMEDIATES |
| | |
| | 10)FL BLD CODE 2309.6 ATTIC ACCESS, PRO- |
| | VIDE ATTIC ACCESS 20"X36". |
| | |
| | 11)FL BLD CODE 2405.2 HAZARDOUS LOCATION |
| | PROVIDE SAFETY GLASS FOR THIS LOCATION: |
| | MASTER BATH, |
| | |
| | 12)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 13)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |