| Plan Review Notes For Permit 02090198 |
| Permit Number |
02090198 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-11 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND MAKE ANY NECESSARY | | | CHANGES ON THE PLANS UPON APPLICATION | | | FOR THE ELECTRICAL PERMIT.RESUBMIT WITH | | | SAME. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|