Plan Review Notes
Plan Review Notes For Permit 02090190
Permit Number 02090190
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-25 00:00:00***********UNSAT ****************
  
 1)NOTE: PLEASE NOTE NO EQUIPMENT GROUND-
 ING CONDUCTOR BETWEEN MAIN DISCONNECTS
 AND METER. THIS WOULD BE PARALLELING THE
 NEUTRAL. PER 250-24
  
 2)NOTE: PLEASE SEE PANEL "B". PLEASE
 CORRELATE LOADS SHOWN FOR A/C #3.
 PLEASE ADJUST LOAD CALCS.
  
 3)NOTE: PLEASE SEE PANEL AND RISER
 DIAGRAM. PLEASE NOTE PANELS SHOWN W/MCB
 AND RISER SHOWN AS MLO? PLEASE CORRELATE
  
 4)NOTE: PLEASE CLARIFY NOTE ON LOWER
 RIGHT HAND CORNER, NOTING GAS WATER
 HEATER? SHOWN AS ELEC ON PANEL SCHEDULE?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372