| Notes |
| Date |
Text |
| 2002-09-25 00:00:00 | ***********UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE NO EQUIPMENT GROUND- | | | ING CONDUCTOR BETWEEN MAIN DISCONNECTS | | | AND METER. THIS WOULD BE PARALLELING THE | | | NEUTRAL. PER 250-24 | | | | | | 2)NOTE: PLEASE SEE PANEL "B". PLEASE | | | CORRELATE LOADS SHOWN FOR A/C #3. | | | PLEASE ADJUST LOAD CALCS. | | | | | | 3)NOTE: PLEASE SEE PANEL AND RISER | | | DIAGRAM. PLEASE NOTE PANELS SHOWN W/MCB | | | AND RISER SHOWN AS MLO? PLEASE CORRELATE | | | | | | 4)NOTE: PLEASE CLARIFY NOTE ON LOWER | | | RIGHT HAND CORNER, NOTING GAS WATER | | | HEATER? SHOWN AS ELEC ON PANEL SCHEDULE? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|