2002-09-11 00:00:00***************** UNSAT *************
  
 PLEASE NOTE PLANS ARE SUBMITTED FOR
 PLAN REVIEW. PLEASE SEE COMMENTS FROM
 ALL REVIEWERS DUE TO CHANGE IN USE OF
 OCCUPANCY. RES APT/ TO OFFICE/STUDIO.
 IMPACT FEES MAY BE DUE. PLEASE SEE BLDG
 COMMENTS.
  
  
 1)NOTE: PLEASE NOTE ALL LOAD CALCULATION
 -S NEED TO BE SHOWN FOR COMMERCIAL USE
 AS PER 220-3,220-100,220-11,220-13,
 PLEASE ALSO NOTE ALL CONTINOUS LOADS
 125% 215-3/230-42
 PLEASE NOTE ALL TRACK LIGHTING PER
 220-12?
  
 2)NOTE: PLEASE NOTE, SOME ITEMS SHOWN ON
 PLANS AS N (NEW) AND E (EXISTING) AND
 OTHER ITEMS WITH NO INDICAITON? PLEASE
 CLARIFY.
 PLEASE SHOW WORK/EXISTING ELEC TO BE
 REMOVED/DEMO.
  
 3)NOTE: PLEASE NOTE MISSING EXIT/EM LTS?
 PLEASE ALSO SEE FIRE REVIEW
 COMMENTS FOR ANY THAT ARE/MAY BE REQ`D.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372