| Plan Review Notes For Permit 02090179 |
| Permit Number |
02090179 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-11 00:00:00 | ***************** UNSAT ************* | | | | | | PLEASE NOTE PLANS ARE SUBMITTED FOR | | | PLAN REVIEW. PLEASE SEE COMMENTS FROM | | | ALL REVIEWERS DUE TO CHANGE IN USE OF | | | OCCUPANCY. RES APT/ TO OFFICE/STUDIO. | | | IMPACT FEES MAY BE DUE. PLEASE SEE BLDG | | | COMMENTS. | | | | | | | | | 1)NOTE: PLEASE NOTE ALL LOAD CALCULATION | | | -S NEED TO BE SHOWN FOR COMMERCIAL USE | | | AS PER 220-3,220-100,220-11,220-13, | | | PLEASE ALSO NOTE ALL CONTINOUS LOADS | | | 125% 215-3/230-42 | | | PLEASE NOTE ALL TRACK LIGHTING PER | | | 220-12? | | | | | | 2)NOTE: PLEASE NOTE, SOME ITEMS SHOWN ON | | | PLANS AS N (NEW) AND E (EXISTING) AND | | | OTHER ITEMS WITH NO INDICAITON? PLEASE | | | CLARIFY. | | | PLEASE SHOW WORK/EXISTING ELEC TO BE | | | REMOVED/DEMO. | | | | | | 3)NOTE: PLEASE NOTE MISSING EXIT/EM LTS? | | | PLEASE ALSO SEE FIRE REVIEW | | | COMMENTS FOR ANY THAT ARE/MAY BE REQ`D. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|