2002-11-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02090128
 ADD: 1386 N MANGONIA DR
 CONT: O/B CURTIS CRAWFORD
 TEL: (561)833-9457
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY BETWEEN SOILS ENGINEER AND
 THE ENGINEER OF RECORD, ( HELICAL AN-
 CHORS). THE SOILS ENGINEER STATES IN HIS
 REPORT THE ANCHORS TO BE SPACED8'-10'
 APART & A INSTALLATION DEPTH OF 25' BE-
 LOW GRADE. THE ENGINEER OF RECORD INDI-
 CATES A MINIMUM OF 12' BELOW GRADE. THE
 ENGINEER OF RECORD DOESN'T INDICATE THE
 TOTAL LENGTHOF THE HELICAL STEEL PIER,
 THE AUGER SIZE TO BE USED, THE AMOUNT
 OF DISK, DIAMETER OF DISK, THE TYPE OF
 ATTACHMENT TO THE FOUNDATION, TO BE RE-
 VIEWED BY THE SOILS ENGINEER BEFORE SUB-
 MITTAL TO BUILDING DEPARTMENT.
  
 1804.1.7 FBC AMENDMENTS, MONOLITHIC SLAB
 SHALL BE A MINIMUM OF 4" ABOVE THE
 FINISH GRADE, AT THE PERIMETER OF THE
 BUILDING.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026