Plan Review Notes
Plan Review Notes For Permit 02090115
Permit Number 02090115
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECCESARY CHANGES
 ON THE PLANS,AND RESUBMIT FOR REVIEW.
  
 1} INDICATE HOW PANEL "B" IS BEING FED.
 PANEL "A" DOES NOT HAVE A BREAKER
 LISTED FOR IT AND IS NOT LISTED AS A
 FEED THROUGH.
  
 2} INDICATE THE CONDUIT & WIRE SIZE
 FEEDING PANEL "B".
  
 4} INDICATE THE OCP OF THE MAIN
 (3/0=225AMPS).
  
 5} PLEASE INDICATE THE MAIN DISCONNECT
 LOCATION ON THE PLANS.NOTE
 230-70(A)C.W.P.B..
  
 6} THE PLANS SHOW A SERVICE-
 LATERAL,PLEASE NOTE 680-10 REGARDING
 THE POOL.
  
 7} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3,ON THE PANEL
 SCHEDULE.
  
 8} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 9} PLEASE NOTE THE BATH GFI'S REQUIRED
 BY 210-11(C)(3) MUST ALSO COMPLY WITH
 210-52(D).THESE RECEPTACLE LOCATIONS
 NEED TO BE SHOWN ON THE PLANS.
  
 10} THE DETACHED GARAGE MUST COMPLY WITH
 225-31.ALSO SEE 250-32(A) EXEPTION.
  
 11} ALL EQUIPMENT MUST COMPLY WITH
 110-26 EG: DISCONNECTS FOR CONDENSERS.
  
 12} KITCHEN ISLAND TO COMPLY WITH
 210-52(C)(2).
  
 IF THERRE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392