| Plan Review Notes For Permit 02082080 |
| Permit Number |
02082080 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-09 00:00:00 | PROVISO: | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | | AREA BEING VENTILATED) OR TABLE 403.3 | | | FOR MECHANICAL VENTILATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|