Plan Review Notes For Permit 02082013
Permit Number 02082013
Review Stop P
Sequence Number 2
Notes
Date Text
2002-10-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) FROM PREVIOUS REVIEW: SHT A1.2 BREAK
 ROOM (108), SINK SHALL COMPLY WITH SECTI
 ON 11-4.24. SHOW HEIGHT 11-4.24.2, KNEE
 CLEARANCE 11-4.24.3, AND CLEAR FLOOR
 SPACE 11-4.24.5 ECT. ALSO DOOR SHALL NOT
 SWING OPEN INTO CLEAR FLOOR SPACE OF ANY
 FIXTURE.
 2) PLEASE SUBMIT GAS CHART USED. FBC-
 2001 FUEL GAS CHARTS ONLY GO UP TO 200'
 AND TOTAL DEVELOPED LENGTH IS APPROX
 400 FEET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377