| Plan Review Notes For Permit 02082013 |
| Permit Number |
02082013 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-10-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) FROM PREVIOUS REVIEW: SHT A1.2 BREAK | | | ROOM (108), SINK SHALL COMPLY WITH SECTI | | | ON 11-4.24. SHOW HEIGHT 11-4.24.2, KNEE | | | CLEARANCE 11-4.24.3, AND CLEAR FLOOR | | | SPACE 11-4.24.5 ECT. ALSO DOOR SHALL NOT | | | SWING OPEN INTO CLEAR FLOOR SPACE OF ANY | | | FIXTURE. | | | 2) PLEASE SUBMIT GAS CHART USED. FBC- | | | 2001 FUEL GAS CHARTS ONLY GO UP TO 200' | | | AND TOTAL DEVELOPED LENGTH IS APPROX | | | 400 FEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|