| Date |
Text |
| 2002-09-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) SHT A1.2 BREAK ROOM (108), SINK SHALL |
| | COMPLY WITH SECTION 11-4.24. SHOW HEIGHT |
| | 11-4.24.2, KNEE CLEARANCE 11-4.24.3, |
| | CLEAR FLOOR SPACE, 11-4.24.5 ECT. |
| | 2) SHT A1.2 DEVELOPING SINK, IS THERE A |
| | DILLUTION TANK FOR THE CHEMICALS USED? |
| | 3) SHT P2.1 KEY NOTES #2 & #3, ALL DEMO. |
| | WORK SHALL BE INSPECTED PRIOR TO COVER- |
| | ING. |
| | 4) SHT P2.1 KEY NOTES #6, GAS SHALL BE |
| | ON SEPARATE PERMIT. (SEE F0LLOWING FOR |
| | GAS PERMIT APPLICATION INFORMATION RE- |
| | QUIREMENTS. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | FBC-2001 FUEL GAS CODE SEC. 401.8 THRU |
| | 402.5.2 & TABLES 402(1)THRU 402(34). |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A-USE OF |
| | CAPACITY TABLES(A)(3). |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2 IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 7-A) PLEASE INDICATE TOTAL APPLIANCES |
| | WITH BTU'S ON EXISTING PORTION OF GAS |
| | SYSTEM. PROVIDE COMPLETE GAS RISER DIA-G |
| | RAM WITH ALL GAS OUTLETS WITH BTU'S FOR |
| | EACH OUTLET. |
| | 5) PLEASE SUBMIT MORE INFORMATION ON THE |
| | OXYGEN SYSTEM. PLEASE INDICATE THE WORK- |
| | ING PRESSURE OF THE OXYGEN SYSTEM. |
| | 6) SEPARATE PERMITS REQUIRED FOR IRRIGA- |
| | TION AND BACKFLOW. PLUMBING CONTRACTOR |
| | SHALL INSTALL BACKFLOW FOR IRRIGATION |
| | CONTRACTOR. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |