2002-09-26 00:00:00DENIED:(1ST PLAN CHECK)
  
 1.PLEASE CLARIFY PLAN SHEET A1.3, "NEW
 PARTITIONS TYPE 1 TYP.PLAN SHEET
 A1.1 INDICATES THE AFOREMENTIONED
 PARTITIONS AS A TYPE 2 NON RATED
 STUD WALL. AS PER 2001 FBC(M)607.1.2
 FIRE DAMPERS ARE REQUIRED FOR DUCTS
 PENETRATING WALLS OR PARTITIONS
 HAVING A FIRE RESISTANCE RATING OF
 1 OR MORE HOURS.
  
 2.PLEASE PROVIDE ADDITIONAL
 INFORMATION ON THE ACID, PROVIDE
 MSDS FOR ACID BEING USED.
  
 3.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 2001 FBC(M) 501.4.
  
 4.WHAT IS BEING STORED IN ROOM 110?
  
 5.PROVIDE SUBMITTAL DATA FOR THE
 FLAMMABLE STORAGE CABINET.
  
 6.DUCT SMOKE DETECTORS REQUIRED FOR
 UNIT OR COMBINED UNITS WITH THE
 DESIGN CAPACITY GREATER THAN 2,000
 CFM (2001 FBC(M) 606.2.1 & 606.2.2).
  
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR HOOD/FIRE SUPRESSION/GAS/WALK-IN
 COOLER/FREEZERS.
  