| Plan Review Notes For Permit 02082013 |
| Permit Number |
02082013 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-26 00:00:00 | DENIED:(1ST PLAN CHECK) | | | | | | 1.PLEASE CLARIFY PLAN SHEET A1.3, "NEW | | | PARTITIONS TYPE 1 TYP.PLAN SHEET | | | A1.1 INDICATES THE AFOREMENTIONED | | | PARTITIONS AS A TYPE 2 NON RATED | | | STUD WALL. AS PER 2001 FBC(M)607.1.2 | | | FIRE DAMPERS ARE REQUIRED FOR DUCTS | | | PENETRATING WALLS OR PARTITIONS | | | HAVING A FIRE RESISTANCE RATING OF | | | 1 OR MORE HOURS. | | | | | | 2.PLEASE PROVIDE ADDITIONAL | | | INFORMATION ON THE ACID, PROVIDE | | | MSDS FOR ACID BEING USED. | | | | | | 3.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 2001 FBC(M) 501.4. | | | | | | 4.WHAT IS BEING STORED IN ROOM 110? | | | | | | 5.PROVIDE SUBMITTAL DATA FOR THE | | | FLAMMABLE STORAGE CABINET. | | | | | | 6.DUCT SMOKE DETECTORS REQUIRED FOR | | | UNIT OR COMBINED UNITS WITH THE | | | DESIGN CAPACITY GREATER THAN 2,000 | | | CFM (2001 FBC(M) 606.2.1 & 606.2.2). | | | | | | PLEASE NOTE ADDITIONAL PERMITS REQUIRED | | | FOR HOOD/FIRE SUPRESSION/GAS/WALK-IN | | | COOLER/FREEZERS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|