| Plan Review Notes For Permit 02082013 |
| Permit Number |
02082013 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-12 00:00:00 | 1) PLEASE EXPLAIN NOTE ON DRAWING | | | " EXISTING WINDOW BARS TO BE REMOVED | | | TO ALLOW FOR EMERGENCY ESCAPE". PLEASE | | | INDICATE ON PLANS IF THE EXISTING | | | WINDOWS IN THESE LOCATIONS ARE CODE | | | COMPLIANT FOR EMERGENCY EGRESS. | | | | | | 2) IT APPEARS THAT A DOOR SIWNGS TOO | | | FAR INTO CORRIDOR 101. | | | | | | 3) PANIC HARDWARE REQUIRED ON ALL EXIT | | | DOORS SUBJECT TO AN OCCUPANCY OF 100 | | | OR MORE PERSONS. | | | | | | 4) IS THE FACP LOCATED IN CORRIDOR 101 | | | NEW OR EXISTING. | | | | | | 5) ALL NEW ELECTRICAL, MECHANICAL OR | | | SERVICE TYPE ROOMS ARE TO BE AT LEAST | | | ONE HOUR RATED IF SPRINKLER HEADS ARE | | | NOT PRESENT. | | | | | | 6) IS THE SS VENT HOOD NEW OR EXISTING | | | AND WHAT WILL IT BE USED FOR. | | | | | | 7) PLEASE EXPLAIN USE OF PROJECTIONS | | | THAT ARE LOCATED IN EXISTING MAIN | | | GALLERY IN FRONT OF DOORS. | | | | | | 8) DUCT SMOKE DETECTORS ARE REQUIRED IN | | | AIR HANDLING UNITS AT 2000 CFM CAPACITY | | | OR ABOVE. | | | | | | 9) PLEASE INDICATE LOCATIONS OF ANY | | | EXISTING EMERGENCY LIGHTS OR EXIT | | | SIGNS IN MONTGOMERY HALL. | | | | | | 10) PLEASE PROVIDE MORE DETAILS ON | | | OXYGEN TANKS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|