2002-09-12 00:00:001) PLEASE EXPLAIN NOTE ON DRAWING
 " EXISTING WINDOW BARS TO BE REMOVED
 TO ALLOW FOR EMERGENCY ESCAPE". PLEASE
 INDICATE ON PLANS IF THE EXISTING
 WINDOWS IN THESE LOCATIONS ARE CODE
 COMPLIANT FOR EMERGENCY EGRESS.
  
 2) IT APPEARS THAT A DOOR SIWNGS TOO
 FAR INTO CORRIDOR 101.
  
 3) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
  
 4) IS THE FACP LOCATED IN CORRIDOR 101
 NEW OR EXISTING.
  
 5) ALL NEW ELECTRICAL, MECHANICAL OR
 SERVICE TYPE ROOMS ARE TO BE AT LEAST
 ONE HOUR RATED IF SPRINKLER HEADS ARE
 NOT PRESENT.
  
 6) IS THE SS VENT HOOD NEW OR EXISTING
 AND WHAT WILL IT BE USED FOR.
  
 7) PLEASE EXPLAIN USE OF PROJECTIONS
 THAT ARE LOCATED IN EXISTING MAIN
 GALLERY IN FRONT OF DOORS.
  
 8) DUCT SMOKE DETECTORS ARE REQUIRED IN
 AIR HANDLING UNITS AT 2000 CFM CAPACITY
 OR ABOVE.
  
 9) PLEASE INDICATE LOCATIONS OF ANY
 EXISTING EMERGENCY LIGHTS OR EXIT
 SIGNS IN MONTGOMERY HALL.
  
 10) PLEASE PROVIDE MORE DETAILS ON
 OXYGEN TANKS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL