2002-09-17 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY/VERIFY FEEDS AND/
 OR LOADS FOR "AC" AND "AA. PLEASE NOTE
 POWER PLANS SHOW BOTH AT 225A AND RISER
 SHOWS W/ 150A DISC`S FEEDING.
 PLEASE SUBMIT THE PANEL SCHEDULEOR
 LOADS THAT ARE EXISTING AND BEING ADDED.
  
  
 2)NOTE: PLEASE NOTE PLANS SHOW ADDING
 NEW "DP" REPLACING OLD ,,? ,,(WHAT SIZE)
 PANEL AC? PLEASE CLARFIY LOAD ON MAIN
 SERVICE AND SIZE OF EXISTING SERVICE
 ENTRANCE CONDUCTORS.?
  
 3)NOTE: PLEASE SEE FIRE AND MECH REVIEW
 COMMENTS THAT MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW