Plan Review Notes
Plan Review Notes For Permit 02082011
Permit Number 02082011
Review Stop B
Sequence Number 2
Notes
Date Text
2002-10-18 00:00:00DENIED BY BUILDING
  
 1)THE WIND LOAD DESIGN CRITERIA CONTAINS
 INCORRECT INFORMATION. PLEASE REVISE.
 - THE BUILDING IMPORTANCE FACTOR IS .77
 - THE BUILDING CATEGORY IS I
 - THE INTERNAL PRESSURE IS + OR - .18
 FOR AN ENCLOSED STRUCTURE
  
 2) SPECIFY THE ROOF SHEATHING ATTACHMENT
 REQUIRED BY THE CITY OF WPB AMENDMENTS
 TO FBC TABLE 2306.1. INDICATE THE
 FASTENER AND THE SPACING THAT IS
 REQUIRED.
  
 3) INDICATE THE POSITIVE AND NEGATIVE
 WIND LOAD PRESSURES FOR ALL EXTERIOR
 OPENINGS ON THE PLANS. ONLY THE NEGATIVE
 PRESSURES HAVE BEEN INDICATED.
  
 4) INDICATE ON THE PLANS THE MIN. SOIL
 BEARING CAPACITY REQUIRED TO SUPPORT THE
 STRUCTURE.
  
 5) THE PLANS MUST BE APPROVED BY THE
 CITY HISTORIC PRESERVATION DEPT. AND BE
 STAMPED AND SIGNED BY THEM.
  
 6) PLEASE REVISE THE REFERENCE TO THE
 FBC IN THE NOTES BELOW THE ROOF FRAMING
 PLAN FROM 2002 TO 2001.
  
 7) ADDITIONAL PERMITS (WITH ADDITIONAL
 FEES) WILL BE REQUIRED FOR THE WINDOWS,
 DOORS, STORM PANELS, PLUMBING AND
 ELECTRICAL AS YOU HAVE INDICATED ON THE
 PLANS.
  
 8) PLEASE RETURN OLD PLANS WHEN
 RESUBMITTING NEW PLANS, IN ORDER TO
 EXPEDIATE REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202