| 2002-10-18 00:00:00 | DENIED BY BUILDING |
| | |
| | 1)THE WIND LOAD DESIGN CRITERIA CONTAINS |
| | INCORRECT INFORMATION. PLEASE REVISE. |
| | - THE BUILDING IMPORTANCE FACTOR IS .77 |
| | - THE BUILDING CATEGORY IS I |
| | - THE INTERNAL PRESSURE IS + OR - .18 |
| | FOR AN ENCLOSED STRUCTURE |
| | |
| | 2) SPECIFY THE ROOF SHEATHING ATTACHMENT |
| | REQUIRED BY THE CITY OF WPB AMENDMENTS |
| | TO FBC TABLE 2306.1. INDICATE THE |
| | FASTENER AND THE SPACING THAT IS |
| | REQUIRED. |
| | |
| | 3) INDICATE THE POSITIVE AND NEGATIVE |
| | WIND LOAD PRESSURES FOR ALL EXTERIOR |
| | OPENINGS ON THE PLANS. ONLY THE NEGATIVE |
| | PRESSURES HAVE BEEN INDICATED. |
| | |
| | 4) INDICATE ON THE PLANS THE MIN. SOIL |
| | BEARING CAPACITY REQUIRED TO SUPPORT THE |
| | STRUCTURE. |
| | |
| | 5) THE PLANS MUST BE APPROVED BY THE |
| | CITY HISTORIC PRESERVATION DEPT. AND BE |
| | STAMPED AND SIGNED BY THEM. |
| | |
| | 6) PLEASE REVISE THE REFERENCE TO THE |
| | FBC IN THE NOTES BELOW THE ROOF FRAMING |
| | PLAN FROM 2002 TO 2001. |
| | |
| | 7) ADDITIONAL PERMITS (WITH ADDITIONAL |
| | FEES) WILL BE REQUIRED FOR THE WINDOWS, |
| | DOORS, STORM PANELS, PLUMBING AND |
| | ELECTRICAL AS YOU HAVE INDICATED ON THE |
| | PLANS. |
| | |
| | 8) PLEASE RETURN OLD PLANS WHEN |
| | RESUBMITTING NEW PLANS, IN ORDER TO |
| | EXPEDIATE REVIEW. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |