Plan Review Notes
Plan Review Notes For Permit 02082011
Permit Number 02082011
Review Stop B
Sequence Number 1
Notes
Date Text
2002-09-24 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) PROVIDE BUCK ATTACHMENT DETAILS FOR
 EXTERIOR WINDOWS, DOORS AND OVERHEAD
 GARAGE DOOR.
  
 4) THE ROOF SHEATHING NAIL SPACING IS
 INCORRECT. THE CITY OF WPB AMENDMENTS TO
 THE FBC TABLE 2306.1 REQUIRES 8D COMMON
 NAILS SPACED 6"O.C. AT EDGES AND 6" O.C.
 INTERMEDIATE IN ZONES 1&2. PLEASE
 CORRECT.
  
 5) INDICATE THE LOCATION AND SPACING OF
 ALL VERTICLE REINFORCEMENT. (REQUIRED AT
 CORNERS AND EACH SIDE OF OPENINGS)
  
 6) THE USP JRSX CONNECTORS PROVIDE 1180#
 OF UPLIFT RESISTANCE. THE 1735# IS FOR
 FLOOR LOAD. PLEASE REVISE PLANS.
  
 7) THE PLANS SPECIFY 10J COMMON NAILS. I
 AM NOT FAMILIAR WITH THE "J" DESIGNATION
 PLEASE CLARIFY.
  
 8) PROVIDE CONSTRUCTION DETAILS THAT
 INDICATE THE CONSTRUCTION OF THE PARAPET
 CORNER DETAILS. (MATERIALS,ATTACHMENTS,
 ETC.)
  
 9) INDICATE THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR ALL EXTERIOR
 WALL OPENINGS ON THE PLANS.
  
 10) THE PLUMBING, ELECTRIC AND WINDOW &
 DOOR INSTALLATION WILL REQUIRE SEPARATE
 PERMITS(WITH ADDITIONAL FEES) AS YOU
 HAVE INDICATED ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202