| 2002-09-04 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE COMPLY WITH THE FOLLOWING ITEMS | | | THAT WERE NOT CLARIFIED ON THE PLANS. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER | | | 110-9,SUBMIT SAME BEFORE CALLING | | | INSPECTION.(MAY BE FAXED TO MY | | | ATTENTION @ 659-8026). | | | | | | 2} PLEASE NOTE ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECT--ED PER 210-8-A-6. | | | INCLUDES KITCHEN ISLANDS.LIST ON SCHED. | | | | | | 3} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG,ON THE PANEL | | | SCHEDULE (IN THE RESIDENCE)BEFORE | | | CALLING INSPECTION. | | | | | | 4} PLEASE NOTE FRONT AND REAR | | | RECEPTS REQ`D PER 210-52E | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 210-12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|