| Plan Review Notes For Permit 02081866 |
| Permit Number |
02081866 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A-1.0 PLEASE SHOW CLEAR FLOOR | | | SPACE FOR BREAK AREA SINK ROOM #403. IF | | | PARALLEL APPROACH THE SINK SHALL BE REQ- | | | UIRED TO BE CENTERED IN THE 48" LENGTH | | | AT 2'. IF FRONTAL APPROACH SHOW DETAIL | | | FOR 11-4.24.3 KNEE CLEARANCE, 11-4.24.5, | | | CLEAR FLOOR SPACE, 11-4.24.6 EXPOSED | | | PIPES AND SURFACES ECT. | | | 2) SHT P-1 WATER ISOMETRIC, WATER HAMMER | | | ARRESTOR SHALL BE LOCATED NEAR THE FIX- | | | TURE IN AN "EFFECTIVE RANGE" NOT AT TOP | | | OF DROP AS SHOWN PER PDI WH-201 AND MAN- | | | UFACTURE INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|