Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-08-27 00:00:001) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING EQUIPMENT IF EXISTING ARE TO
 BE BROUGHT TO FULL WORKING ORDER.
  
 2) INTERIOR FINISH IN EXITS TO BE CLASS
 A, AND A OR B IN OTHER AREAS.
  
 3) PANIC HARDWARE REQUIRED ON EXIT
 DOORS.
  
 4) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS.SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM EQUIPMENT.
  
 5) REMOVE STAGE AND STAIRS OR MEET
 ALL REQUIREMENTS OF THE FLORIDA
 BUILDING AND FIRE CODES.
  
 6) NO COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS WILL BE ALLOWED
 UNLESS AN APPROVED HOOD,DUCT,AND
 EXTINGUISHING SYSTEM IS INSTALLED.
 PROVIDE SEPARATE PLANS AND PERMITS PRIOR
 TO INSTALLATION.
  
 7) NO OCCUPANT LOADS PROVIDED.ACCORDING
 TO INFORMATION PROVIDED, THE DIRECTOR
 OF CONSTRUCTION SERVICES HAS LIMITED
 THE OCCUPANT LOAD AT 200 PERSONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910