 BUILDING PLAN REVIEW
 PERMIT: 02081856
 ADD: 7919 S DIXIE
 SUITE: 7631/ 7629
 CONT: E.L.C.I. CONSTRUCTION GROUP
 TEL: (305)868-3333
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****BUILDING PROVISO*****
  
 1) PER THE BUILDING OFFICIAL THE OCCU-
 PANCY SHALL BE SET @ NO MORE THAN 200
 PEOPLE FOR THE TEMPORARY USE OF UNIT FOR
 EDUCATIONAL OCCUPANCY.
 2)TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS; 2 HR OCCUPANCY SEPERATION
 REQUIRED, PROVIDE U. L. LISTING FOR THE
 2 HR RATED WALL.
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 4)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
 5)705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
 6) 1021.3.1 PANIC AND FIRE EXIT HARDWARE
 REQUIRED FOR MEANS OF EGRESS, EDUCATION-
 AL OCCUPANCY.
 7) 11-5.2 WHERE FOOD OR DRINK IS SERVED
 AT COUNTERS EXCEEDING 34" IN HEIGHT FOR
 CONSUMPTION, A PORT5ION OF THE MAIN
 COUNTER WHICH IS 60" IN LENGTH MINIMUM
 SHALL BE PROVIDED IN COMPLIANCE WITH
 11-4.32 OR SERVICE SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.
  
 8) REMOVAL OF PLATFORM, OTHERWISE COMPLI
 ANCE WITH VERTICAL ACCESSIBILITY SHALL
 BE REQUIRED, ALSO GUARDRAILS AND HAND
 SHALL BE REQUIRED AS PROPOSED IN SECTION
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412