2002-08-27 00:00:001) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHT FIXTURES IF EXISTING ARE TO BE
 BROUGHT TO FULL WORKING ORDER.
  
 2) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A, AND OTHER AREAS SHALL BE CLASS
 A OR B.
  
 3) DRAWINGS DO NOT INDICATE FIRE ALARM
 EQUIPMENT. SEPARATE PLANS AND PERMITS
 REQUIRED FOR THE INSTALLATION OF FIRE
 ALARM EQUIPMENT.
  
 4) PANIC HARDWARE REQUIRED ON EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
  
 5) PLANS DO NOT INDICATE OCCUPANCY LOAD.
 ACCORDING TO PAPERWORK FROM CONSTRUCTION
 SERVICES, THE DIRECTOR OF THAT
 DEPARTMENT HAS SET THE OCCUPANT LOAD
 AT 200 STUDENTS.
  
 6) NO COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS ARE ALLOWED UNLESS
 AN APPROVED HOOD,DUCT,AND EXTINGUISHING
 SYSTEM IS INSTALLED. SEPARATE PLANS
 AND PERMITS REQUIRED PRIOR TO
 INSTALLATION.
  
 7) PLANS DO NOT INDICATE THE FIRE RATING
 OF ONE OF THE TENANT DEMISING WALLS.
  
 8) FIRE DRILLS ARE REQUIRED TO BE
 PERFORMED.
  
 9) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  