| Plan Review Notes For Permit 02081855 |
| Permit Number |
02081855 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-27 00:00:00 | 1) ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHT FIXTURES IF EXISTING ARE TO BE | | | BROUGHT TO FULL WORKING ORDER. | | | | | | 2) INTERIOR FINISH IN EXITS SHALL BE | | | CLASS A, AND OTHER AREAS SHALL BE CLASS | | | A OR B. | | | | | | 3) DRAWINGS DO NOT INDICATE FIRE ALARM | | | EQUIPMENT. SEPARATE PLANS AND PERMITS | | | REQUIRED FOR THE INSTALLATION OF FIRE | | | ALARM EQUIPMENT. | | | | | | 4) PANIC HARDWARE REQUIRED ON EXIT | | | DOORS SUBJECT TO AN OCCUPANCY OF 100 | | | OR MORE PERSONS. | | | | | | 5) PLANS DO NOT INDICATE OCCUPANCY LOAD. | | | ACCORDING TO PAPERWORK FROM CONSTRUCTION | | | SERVICES, THE DIRECTOR OF THAT | | | DEPARTMENT HAS SET THE OCCUPANT LOAD | | | AT 200 STUDENTS. | | | | | | 6) NO COOKING THAT PRODUCES SMOKE OR | | | GREASE LADEN VAPORS ARE ALLOWED UNLESS | | | AN APPROVED HOOD,DUCT,AND EXTINGUISHING | | | SYSTEM IS INSTALLED. SEPARATE PLANS | | | AND PERMITS REQUIRED PRIOR TO | | | INSTALLATION. | | | | | | 7) PLANS DO NOT INDICATE THE FIRE RATING | | | OF ONE OF THE TENANT DEMISING WALLS. | | | | | | 8) FIRE DRILLS ARE REQUIRED TO BE | | | PERFORMED. | | | | | | 9) PORTABLE FIRE EXTINGUISHERS ARE | | | REQUIRED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|