| 2003-02-06 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | --INFORMATIVE-- |
| | FBC 3401.7.2.5REPAIRS AND ALTERATIONS |
| | AMOUNTING TO OVER 25% BUT NOT EXCEEDING |
| | 50% OF THE EXISTING BUILDING'S VALUE CAN |
| | BE MADE WITHOUT MAKING THE ENTIRE |
| | EXISTING BUILDING COMPLY, PROVIDED SUCH |
| | REPAIRS AND ALTERATIONS COMPLY WITH THE |
| | REQUIREMENTS OF THE CODE.SEE PROVISOS |
| | BELOW. |
| | |
| | --PROVISO-- |
| | FBC 1005.4.1EGRESS WINDOWS.THE |
| | REPLACEMENT BEDROOM WINDOWS SHALL BE |
| | EGRESS WINDOWS WITH A MIN. CLEAR OPENING |
| | OF 24" HIGH X 20" WIDE BUT NOT LESS THAN |
| | 5.7 SQ FT. |
| | |
| | --PROVISO-- |
| | FBC 1707.4.2.1 PROVIDE PRODUCT APPROVALS |
| | FOR THE REPLACEMENT WINDOWS AND EXTERIOR |
| | DOORS. |
| | |
| | --PROVISO-- |
| | FBC 2405.2THE REPLACEMENT BATHROOM |
| | WINDOW GLAZING IS IN A 'HAZARDOUS |
| | LOCATION' AND IS REQUIRED TO BE SAFETY |
| | GLASS SATISFYING THE REQUIREMENTS OF THE |
| | CONSUMER PRODUCT SAFETY COMMISSION 16, |
| | CODE OF FEDERAL REGULATIONS, PART 1201 |
| | (CPSC 16-CFR, PART 1201). |
| | |
| | --PROVISO-- |
| | FBC 2309.6ATTIC ACCESS OPENING. |
| | NOTE 10 STATES "THIS CEILING HAS BEEN |
| | REPLACED", BUT THIS NOTE HAS NOT BEEN |
| | CALLED UP ANYWHERE ON THE PLANS.IF A |
| | NEW CEILING IS PROPOSED IT SHALL |
| | INCORPORATE AN ATTIC ACCESS OPENING NOT |
| | LESS THAN 20"X30". |
| | |
| | --PROVISO-- |
| | FBC 1606.3SUBMIT A PRODUCT APPROVAL |
| | FOR THE PROPOSED 'FIBERGLAS' SHINGLES. |