Plan Review Notes
Plan Review Notes For Permit 02081845
Permit Number 02081845
Review Stop B
Sequence Number 2
Notes
Date Text
2002-09-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE PLANS AND PERMIT APPLICATION FORM
 SHALL BE AMENDED TO SHOW THE CORRECT
 STREET ADDRESS.BOTH THE CITY'S G.I.S.
 AND THE COUNTY PROPERTY APPRAISER
 LISTINGS SHOW THAT THE ADDRESS
 638 7TH ST DOES NOT EXIST, SHOULD THIS
 BE 628 7TH ST?
  
 2) FBC 3401.7.2 INFORMATIVE
 ACCORDING TO THE SUBMITTED PLAN SHEET,
 THE ONLY CONSTRUCTION REFERRED TO AS
 EXISTING IS THE PERIMETER PILINGS AND
 PERIMETER BEAMS (SEE DETAIL D, NOTES 7
 AND 8).REFER ALSO TO COMMENT NO. 1
 FROM THE PREVIOUS PLAN REVIEW DATED
 9/4/02.WITH DUE CONSIDERATION OF
 FBC 3401.7.2 AND FBC* F102.1, THE
 BUILDING OFFICIAL HAS AGREED TO PERMIT
 THIS EXTENSIVE REPAIR TO AN EXISTING
 TYPE VI BUILDING, IN THE FIRE DISTRICT,
 IN ORDER TO ENABLE COMPLIANCE WITH THE
 REQUIREMENTS OF THE HISTORICAL
 PRESERVATION DIVISION.HOWEVER, AS THE
 ALTERATIONS WILL AMOUNT TO MORE THAN 50%
 OF THE VALUE OF THE EXISTING BUILDING,
 IT MUST BE MADE TO CONFORM TO ALL OTHER
 REQUIREMENTS FOR A NEW TYPE VI BUILDING
 (REF. FBC 3401.7.2.6) AS PER THE
 COMMENTS BELOW.
  
 3) FBC 608HORIZONTAL SEPARATION. AMEND
 THE PLANS TO SHOW THE DIMENSION BETWEEN
 EACH EXTERIOR WALL AND THE RELEVANT
 PROPERTY LINE.
  
 4) FBC 1005.4.1EACH BEDROOM SHALL HAVE
 ALTERANATIVE EGRESS, WHICH MAY BE IN THE
 FORM OF EGRESS WINDOWS WITH A MIN. CLEAR
 OPENING OF 24" HIGH X 20" WIDE.
  
 5) FBC 1707.4.2.1PROVIDE PRODUCT
 APPROVALS FOR THE WINDOWS AND EXTERNAL
 DOORS.
  
 6) FBC 2405.2THE BATHROOM WINDOW
 GLAZING IS IN A 'HAZARDOUS LOCATION' AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 7) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 8) FBC 104.2.1.2SPECIFY THE SIZE AND
 THE MATERIAL FOR THE PORCH ROOF SUPPORT
 POSTS.
  
 9) FBC 2309.6ATTIC ACCESS OPENING.
 AMEND THE PLANS TO SHOW AN INTERIOR
 ATTIC ACCESS OPENING NOT LESS THAN
 20"X30".
  
 10) FBC 1606.1.7THE PLANS SHALL STATE
 THE BUILDING CODE (FBC 2001), BASIC WIND
 SPEED (140 MPH), WIND IMPORTANCE FACTOR,
 EXPOSURE CATEGORY, INTERNAL PRESSURE
 COEFFICIENT, AND COMPONENT AND CLADDING
 PRESSURES USED FOR THE SPECIFICATION OR
 DESIGN OF THE ROOF TRUSSES AND ANCHORS
 FOR TRUSSES, WALL STUDS, HEADERS, JACK
 STUDS AND STUD TO BOTTOM PLATE
  
 11) FBC* 1606.1.6DETAIL C, TYPICAL
 FRAME WALL SECTION REFERS TO TRUSSES
 DESIGNED FOR 110 MPH WIND SPEED.UNDER
 FBC 2001 THE WIND SPEED FOR THE CITY OF
 WEST PALM BEACH IS 140 MPH.AMEND PLANS
  
 12) FBC 1606.3 SUBMIT A PRODUCT APPROVAL
 FOR THE PROPOSED FIBER GLASS SHINGLES.
  
 13) FBC* TABLE 2306.1ROOF SHEATHING
 FASTENER SPACING.AMEND DETAIL C TO
 REDUCE THE FASTENER SPACING FOR ZONE 3
 (I.E. WITHIN 5' OF GABLE ENDS) FROM 6"
 TO 4" O.C. AT EDGES.
  
 14) FBC 2307.6.1NO FLOOR SHEATHING IS
 SPECIFIED ON DETAIL C.AMEND THE PLANS
 TO SHOW A MIN. 7/16 WOOD STUCTURAL PANEL
 FLOOR SHEATHING SPECIFICATION.
  
 15) FBC 2307.1ANCHORAGE OF SILL PLATE
 TO FOUNDATION.DETAIL C DOES NOT SHOW A
 SILL PLATE APPLIED TO THE EXISTING
 PERIMETER CONCRETE CAP BEAM OR ANY MEANS
 OF ANCHORING THE SILL PLATE DOWN TO THE
 FOUNDATION SYSTEM.AMEND THE PLANS.
  
 16) FBC 2313.1NO WALL SHEATHING IS
 SHOWN ON THE PLANS.SPECIFY SHEARWALL
 CONSTRUCTION SUFFICIENT TO TRANSMIT WIND
 LOADS TO THE FOUNDATION SYSTEM.
  
 17) FBC 2313.2END WALLS.ANNOTATE THE
 PLANS TO SPECIFY SHEARWALL ANCHORS AT
 THE BASE OF THE SHEARWALL SEGMENTS.
 ALSO, DUE TO THE LACK OF EXTERIOR WALL
 SHEAR CAPACITY AT THE END WALLS,
 INTERIOR WALLS WILL BE REQUIRED TO ACT
 AS SHEARWALLS.SPECIFY WHICH INTERIOR
 WALLS WILL BE USED, AND THE SHEARWALL
 MATERIALS AND NAIL TYPE/SIZE/SPACING.
  
 18) FBC 2313.4GABLE ENDWALL.THE
 GABLE ENDWALL STUDS SHALL BE
 STRUCTURALLY CONTINUOUS UPTO THE ROOF
 SHEATHING, AND FULL DEPTH ROOF BRACING
 SHALL BE PROVIDED AT 4 FT O.C. BETWEEN
 THE FIRST 3 TRUSSES.ALTERNATIVELY, THE
 CEILING SHALL BE REQUIRED TO ACT AS A
 DIAPHRAGM, AND DESIGNED ACCORDINGLY, TO
 PROVIDE LATERAL SUPPORT TO THE STUDS AND
 GABLE END TRUSS.PROVIDE DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 19) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499