2002-10-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 THE FOLLOWING IS A REVIEW OF THE PLAN
 RE-SUBMITTAL MADE IN REPONSE TO JIM
 WITMER'S 9/27/02 PLAN REVIEW COMMENTS.
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THAT PLAN REVIEW.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 104.3.1.1MINIMUM PLAN REVIEW
 CRITERIA.THIS COMMENT WAS NOT
 ADDRESSED.SUBMIT A FLOOR PLAN SHOWING
 ANY CHANGE IN FLOOR LEVEL AT THE FORMER
 GARAGE DOOR LOCATION, THE WIDTH/LOCATION
 OF THE FAMILY ROOM DOORWAY, AND THE
 OVERALL SIZE OF THE PROPOSED FAMILY ROOM
 SO THAT THE MINIMUM REQUIREMENTS FOR
 EGRESS (FBC 1012.1.3 AND TABLE 1004) AND
 FOR LIGHT AND VENTILATION TO THE NEW
 ROOM CAN BE ASSESSED.SUBMIT A CROSS-
 SECTIONAL VIEW OF THE WALL SHOWING THE
 PROPOSED WALL CONSTRUCTION (INCLUDING
 SHEATHING) FROM FOUNDATION/SLAB TO ROOF.
  
 3,4,5) FBC 1606THESE COMMENTS HAVE NOT
 BEEN ADDRESSED.THE PROPOSED 2-1/2"
 TAPCONS WILL NOT HAVE SUFFICIENT
 EMBEDMENT WHEN USED TO ANCHOR DOWN THE
 2"X 4" SILL PLATE.RE-SPECIFY TO ENSURE
 NO LESS THAN 1-1/4" EMBEDMENT. THE PLANS
 DO NOT STATE TO WHAT SUBSTRATE THE SILL
 PLATE IS BEING ATTACHED.IS THERE A
 SLAB AT THIS LOCATION AND WHAT IS THE
 EDGE THICKNESS?THE PROPOSED MEANS OF
 ATTACHMENT FOR THE SIDES AND TOP OF THE
 INFILL WALL FRAMEWORK IS NOT CLEAR FROM
 THE PLANS.CLEARLY SPECIFY THE PROPOSED
 ATTACHMENT METHOD ON THE PLANS.ALSO,
 THE PLANS SHALL SHOW THE EXISTING
 CONSTRUCTION AT THE SIDES OF THE OPENING
 WHICH WILL BE THE SUBSTRATE TO WHICH THE
 NEW WALL WILL BE ATTACHED.THE PLANS
 SHALL SPECIFY THE MEANS OF ATTACHMENT OF
 THE NEW WINDOW TO THE WINDOW BUCK.
  
 THREE DIFFERENT WINDOW PRODUCT APPROVALS
 HAVE BEEN SUBMITTED, INCLUDING BOTH
 ARCHED AND RECTANGULAR WINDOWS.WHICH
 PRODUCT IS TO BE USED?THE APPROPRIATE
 PRODUCT APPROVAL DRAWINGS/TABLES SHALL
 BE MARKED TO SHOW WHICH WINDOW TYPE/SIZE
 IS PROPOSED.SUBMIT TWO COPIES OF THE
 RELEVANT PRODUCT APPROVALS:
 - TEXT SHEETS 2 & 3 AND ALL OF THE
 DRAWING SHEETS SUBMITTED AS PART OF THE
 SERIES PA-14 ALUMINUM SINGLE HUNG WINDOW
 PRODUCT APPROVAL NOA#01-0226.04 ARE FROM
 A DIFFERENT PRODUCT APPROVAL
 (NOA# 97-1027.09) WHICH EXPIRED 7-9-01.
 - DRAWING SHEET 1 OF THE RECTANGULAR
 ALUMINUM FIXED WINDOW PRODUCT APPROVAL
 NOA# 01-0209.11 IS A VERY POOR REDUCED
 SIZE COPY WHICH CANNOT BE READ.ALSO,
 THE 11" X 14" DRAWING SHEET 'PA14....'
 ATTACHED TO THE PRODUCT APPROVAL IS NOT
 PART OF THE APPROVAL DOCUMENT AND SHALL
 BE REMOVED FROM THE PACK.
 - DRAWING SHEET 1 OF THE RADIUS ARCH
 ALUMINUM FIXED WINDOW PRODUCT APPROVAL
 NOA# 01-0209.10 IS AGAIN A VERY POOR
 REDUCED SIZE COPY WHICH CANNOT BE READ.
 THE 11"X 14" DRAWING SHEET 'PA14....'
 ATTACHED TO THE PRODUCT APPROVAL IS NOT
 PART OF THE APPROVAL DOCUMENT AND SHALL
 BE REMOVED FROM THE PACK.
 - SUBMIT TWO COPIES OF AN APPROPRIATE
 CURRENT AND LEGIGLE PRODUCT APPROVAL FOR
 THE WINDOW.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 JIM WITMER(561) 659 8096 EXT 8412
 ROBERT BROWNEXT 8499