| | BUILDING PLAN REVIEW |
| | PERMIT: 02081762 |
| | ADD: 400 NN FLAGLER DR # 505 |
| | CONT: SATURN |
| | TEL: (561)734-9494 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | *****PROVISO****** |
| | |
| | 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 2)1203.4.2 EVERY TOLIET ROOM SHALL |
| | HAVE WINDOWS AS SPECIFIED FOR HABITABLE |
| | ROOMS PROVIDING IN NO CASE LESS THAN 3 |
| | SQ FT OPEN SPACE, OR HAVE APPROVED EQUIV |
| | ALENT VENTILATION. |
| | |
| | 3)1204.3 SHOWERS. SHOWER COMPARTMENTS |
| | SHALL HAVE FLOORS AND WALLS CONSTRUCTED |
| | OF SMOOTH, CORROSION RESISTANT AND NON- |
| | ABSORBENT WATER-RESISTANT MATERIALS TO A |
| | HEIGHT OF NOT LESS THAN 70" ABOVE THE |
| | COMPARTMENT FLOOR AT DRAIN. |
| | |
| | 4)1204.4 JOINTS. BUILT IN TUBS WITH |
| | SHOWERS SHALL HAVE WATER-PROOF JOINTS |
| | BETWEEN THE TUB & WATER RESISTANT WALL. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |