| 2002-10-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW |
| | 1) FBC-2001424.2.7.1 POOL CIRCULATING |
| | PUMPS SHALL BE EQUIPPED ON THE INLET |
| | SIDE WITH AN APPROVED TYPE HAIR AND LINT |
| | STRAINER WHEN USED WITH A PRESSURE FIL- |
| | TER. (DETAIL) |
| | 2) FBC-2001 424.2.8.1 VALVES SHALL BE |
| | MADE OF MATERIALS THAT ARE APPROVED IN |
| | THE FLA BLDG CODE, PLUMBING. THEY WILL |
| | BE READILY ACCESSIBLE FOR MAINT. AND RE- |
| | MOVAL. SEC 424.2.8.2 FULL WAY VALVES |
| | SHALL BE INSTALLED TO INSURE PROPER FUN- |
| | CTION OF THE FILTRATION AND PIPING SYS- |
| | TEM. SEC 424.2.8.3 WHERE CHECK VALVES |
| | ARE INSTALLED THEY SHALL BE OF THE SWING |
| | OR VERTICAL CHECK PATTERNS. SEC 424.2.8. |
| | 4 COMBINATION VALVES SHALL REQUIRE APP- |
| | ROVAL OF THE ADMINISTRATIVE AUTHORITY |
| | PRIOR TO THEIR INSTALLATION. VALVE MISS- |
| | ING FOR (1) MAIN DRAIN LINE. |
| | 3) FBC-2001 424.2.13.2JOINTS AND CON- |
| | NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| | NOTES) |
| | |
| | REVIEW BY KEN STEVENS |