| 2002-09-06 00:00:00 | DENIED: | | | | | | 1.PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3. | | | | | | 2.AS PER 2001 FBC(M) 601.4, PRESSURE | | | DIFFERENTIALS ACROSS CLOSED DOORS | | | WHERE RETURNS ARE CENTRALLY LOCATED | | | SHALL BE LIMITED TO .001 WC OR LESS. | | | PLEASE PROVIDE AIR DUCT PATHWAYS OR | | | AIR TRANSFER PATHWAYS FROM THE HIGH | | | PRESSURE ZONE TO THE LOW ZONE. | | | | | | 3.PROVIDE FAN SHUTDOWN BY DUCT SMOKE | | | DETECTORS IN ACCORDANCE WITH 2001 | | | FBC(M) 606.2.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|