2002-09-06 00:00:00DENIED:
  
 1.PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3.
  
 2.AS PER 2001 FBC(M) 601.4, PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS
 WHERE RETURNS ARE CENTRALLY LOCATED
 SHALL BE LIMITED TO .001 WC OR LESS.
 PLEASE PROVIDE AIR DUCT PATHWAYS OR
 AIR TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW ZONE.
  
 3.PROVIDE FAN SHUTDOWN BY DUCT SMOKE
 DETECTORS IN ACCORDANCE WITH 2001
 FBC(M) 606.2.2.
  