2002-08-29 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY METHOD OF
 EQUIPMENT GROUND FOER NEW PANEL. SIZE
 PER 250-122.
  
 2)NOTE: PLEASE NOTE, NEED LOAD CALCS
 FOR EXISTING PANEL "2S" AND 2T.
 PLANS SHOWING NEW LOADS TO EXISTING
 PANELS. PLEASE CLARIFY
  
 3)NOTE: PLEASE VERIFY MEANS OF DISC
 FOR NEW AHU`S. 440-11.
  
 4)NOTE: PLEASE CLARIFY FIRE REVIEW
 COMMENT. IS THIS GOING TO BE ALL ONE
 TENANT? ACESS FOR PANEL?
  
 5)NOTE: PLEASE CLARIFY SQ FT IN LOAD
 CALCS. 220-3,220-10,220-11,,,,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372