| Notes |
| Date |
Text |
| 2002-09-05 00:00:00 | THE "EXECUTIVE OFFICES" COMPRISE | | | SEPARATE TENANTS, THEREFORE COMPLIANCE | | | WITH FBC704.3.1 IS REQUIRED SINCE IT | | | APPEARS THETOTAL SPACE EXCEEDS THE 3000 | | | SQUARE FEET AREA EXCEPTION.PLEASE | | | REVISE AS NECESSARY. | | | | | | IT APPEARS SEVERAL OF THE PROPOSED | | | OFFICES WILL NOT HAVE THE HC | | | MANEUVERING CLEARANCE AT THE DOORS | | | SHOWN AS (1), AND REQUIRED BY FBC | | | 11-4.13.6. |
|