| 2003-08-12 00:00:00 | *****CORRECTIONS******* |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEE PREVIOUS CORRECTION LIST ITEM |
| | #2, SIGN OWNER/AGENT LINE OF THE ENERGY |
| | CALC. |
| | |
| | 2.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #8.THIS AREA IS ONE OF QUESTIONABLE |
| | SOILS.PROVIDE AN ENGINEER'S REPORT |
| | CERTIFYING THE FOOTERS AND SLAB. |
| | |
| | 3.)ITEM #5 WAS NOT ADDRESSED.SHOW |
| | OPENINGS BETWEEN THE EXISTING HOUSE AND |
| | PORCH.ARE THESE OPENINGS TO BE |
| | ALTERED?IF NOT, IMPACT PROTECTION IS |
| | OPTIONAL.IF THEY ARE BEING CHANGED |
| | (EX: DOOR REMOVED), IMPACT PROTECTION |
| | IS REQUIRED FBC1606.1.4, FBC3401.7.2.4. |
| | |
| | 4.)AS THIS IS AN UNCONVENTIONAL |
| | DESIGN (TIE BEAM ATTACHED TO WOOD BEAM), |
| | HAVE A STRUCTURAL ENGINEER CERTIFY |
| | THE DESIGN. |
| | |
| | 5.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | 16.A FIRESTOP WAS SHOWN IN THE |
| | ROOF JOISTS.SHOW FIRESTOP FOR THE |
| | WALLS, FBC705.3.1. |
| | |
| | 6.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #17.WALL SECTION SHOWS A 1X8, NOTE AT |
| | TOP LEFT OF PLAN SHOWS A 2X8. |
| | |
| | 7.)REFERENCE IS MADE TO "FL BLDG CODE |
| | 3002".REVISE. |
| | |
| | 8.)PROVIDE WIND DESIGN INFORMATION |
| | ON THE PLAN AS REQUIRED FBC1606.1.7. |
| | |
| | 9.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN; EXISTING AND PROPOSED, NEW TOTAL. |
| | |
| | 10.) WHEN RESUBMITTING, SUBMIT ALL OLD |
| | SHEETS AND CLOUD ALL CHANGES TO THE |
| | PLAN. |