| Plan Review Notes For Permit 02081591 |
| Permit Number |
02081591 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-01-21 00:00:00 | PROVISO: | | | | | | PLAN SHEET M2.2 & M3.1, INDICATE DUCT | | | IN THE STAIRWAY, PER 2001 FBC 1006.1.3.1 | | | PENETRATIONS THROUGH A STAIRWAY | | | ENCLOSURE ASSEMBLY ARE PROHIBITED EXCEPT | | | FOR REQUIRED EXIT DOORS, DUCTWORK & | | | EQUIPMENT NECESSARY FOR INDEPENDENT | | | STAIR PRESSURIZATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|