| Plan Review Notes For Permit 02081591 |
| Permit Number |
02081591 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-10-01 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE NOT ALL NOTES FROM | | | FIRST REVIEW WERE ADDRESSED. | | | | | | 2)NOTE: PLEASE NOTE PLAN STILL SHOW | | | CIRCUITS FOR A PANEL 312 AND NO 312 | | | IS SHOWN ON PLANS OR RISER? | | | | | | 3)NOTE: PLEASE NOTE TRACK LIGHTING LOAD | | | CALCS.? CLARIFY | | | | | | 4)NOTE: PLEASE CLARIFY NOTE FROM FIRST | | | REVIEW FOR HOW REQ`MENTS FOR 230-2 | | | ARE MET IN ORDER TO ADD ADDITIONAL | | | SERVICE.? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESITONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|