Plan Review Notes
Plan Review Notes For Permit 02081591
Permit Number 02081591
Review Stop B
Sequence Number 2
Notes
Date Text
2002-10-16 00:00:00SECOND PAID PLAN REVIEW.
  
 THE PROPOSED ELEVATOR AS SHOWN DOES NOT
 COMPLY WITH FBC 3003.4.2.QUOTING THE
 CODE SECTION, "ELEVATOR TO COMPLY W/FBC
 3003.2" IS NOT A SUBSTITUTE FOR
 SPECIFIC DESIGN INFORMATION.SEE FBC
 104.2.1, FBC 3003.4.2 AND FBC 11-4.10
 AND COMPARE THE INFORMATION AS TO
 DIMENSIONSAND DESIGN REQUIREMENTS IN
 THOSE SECTIONS TO THE ELEVATOR PROPOSED
 ON THE PLANS.
  
 THE EXISTING STAIRS IN THE SOUTH WEST
 CORNER OF THE BUILDING AS SHOWN ON
 SHEET A2 AND A3 AS REVISED DO NOT
 COMPLY WITH THE INTENT OF ENCLOSED
 STAIRS IN FBC 1006.1.THE MACHINE ROOM
 ON THE FIRST FLOOR AND THE FILING ROOM
 ON THE SECOND FLOOR ARE SHOWN TO BE
 WIHTIN THE ENCLOSURE WHICH IS
 PROHIBITTED BY FBC 1006.1.3.
  
 THE HISTORIC REVIEW AND COUNTY IMPACT
 REQUIREMENTS ARE UNDERSTOOD TO HAVE
 BEEN PREVIOUSLY ACKNOWLEDGED.