| 2002-10-16 00:00:00 | SECOND PAID PLAN REVIEW. | | | | | | THE PROPOSED ELEVATOR AS SHOWN DOES NOT | | | COMPLY WITH FBC 3003.4.2.QUOTING THE | | | CODE SECTION, "ELEVATOR TO COMPLY W/FBC | | | 3003.2" IS NOT A SUBSTITUTE FOR | | | SPECIFIC DESIGN INFORMATION.SEE FBC | | | 104.2.1, FBC 3003.4.2 AND FBC 11-4.10 | | | AND COMPARE THE INFORMATION AS TO | | | DIMENSIONSAND DESIGN REQUIREMENTS IN | | | THOSE SECTIONS TO THE ELEVATOR PROPOSED | | | ON THE PLANS. | | | | | | THE EXISTING STAIRS IN THE SOUTH WEST | | | CORNER OF THE BUILDING AS SHOWN ON | | | SHEET A2 AND A3 AS REVISED DO NOT | | | COMPLY WITH THE INTENT OF ENCLOSED | | | STAIRS IN FBC 1006.1.THE MACHINE ROOM | | | ON THE FIRST FLOOR AND THE FILING ROOM | | | ON THE SECOND FLOOR ARE SHOWN TO BE | | | WIHTIN THE ENCLOSURE WHICH IS | | | PROHIBITTED BY FBC 1006.1.3. | | | | | | THE HISTORIC REVIEW AND COUNTY IMPACT | | | REQUIREMENTS ARE UNDERSTOOD TO HAVE | | | BEEN PREVIOUSLY ACKNOWLEDGED. |
|