| Plan Review Notes For Permit 02081591 |
| Permit Number |
02081591 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-29 00:00:00 | 1) ARE HANDRAILS PRESENT NEAR STAIRS | | | ADJACENT TO OFFICE 224. | | | | | | 2) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION FOR WALLS AND CEILINGS | | | PROVIDED WITH PLANS. | | | | | | 3) TABLE AND CHAIRS LOCATED IN FRONT | | | OF BREAK ROOM EXIT DOOR. | | | | | | 4) PLEASE INDICATE OCCUPANT LOADS AND | | | A LIFE SAFETY PLAN. | | | | | | 5) PLEASE INDICATE LOCATIONS OF | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | 6) STORAGE ROOMS ARE TO BE FIRE RATED | | | AT LEAST ONE HOUR WITH OPENING | | | PROTECTIVES. | | | | | | 7) THE FIRE ALARM SYSTEM REMODEL TO BE | | | CLASS A, STYLE D NOT CLASS B, STYLE C | | | AS INDICATED IN THE FIRE ALARM NOTES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|