Plan Review Notes
Plan Review Notes For Permit 02081591
Permit Number 02081591
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-04 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY "NEW" SERVICE
 SHOWN ON RISER DIAGRAM. PLEASE SHOW IF
 NEW SERVICE IS COMING FROM THE SAME TRAN
 SFORMER OF EXISTING SERVICE IN ORDER TO
 MEET THE REQ`MENTS OF 230-2.
 PLEASE CLARIFY IF EXISTING ELECTRICAL
 ROOM IS ATTACHED STRUCTUALY. PER 225-31
  
 2)NOTE: PLEASE NOTE CIRCUITING SHOWN FOR
 A PANEL "312", PLEASE NOTE NO PANEL
 312 SHOWN ON RISER? (MISPRINT?)
  
 3)NOTE: PLEASENOTE CIRCUITING FOR
 EMERGENCY LIGHTING TO MEET 700-12-E
  
 4)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO SHOW TRACK LIGHTING PER 220-12B
 ALSO, ALL CONTINUOUS LOADS AND LARGEST
 MOTOR AT 125%. 230-42/215-3 ETC.
  
 5)NOTE: PLEASE CLARIFY NEW OR EXISTING
 GFI FOR ROOFTOP EQUIPMENT PER 210-63
  
 6)NOTE: PLEASE NOTE AN EQUIPMENT GROUND
 IS BEING SHOWN BEFORE THE FIRST MEANS
 OF DISCONNECT AND METER? PLEASE CLARIFY?
 THIS WOULD BE PARALLELING THE NEUTRAL.
 PLEASE ALSO CLARIFY WHY THE NEUTRAL IS
 NOT BEING TAKEN TO THE FIRST MEANS OF
 DISC? REQ`D PER 250-24
  
 7)NOTE: PLEASE NOTE THAT INFORMATION
 WILL BE REQ`D FOR FIXTURE TYPE "D".
 PLEASE NOTE FIXTURE SCHEDULE WILL NEED
 TO BE REVISED.
  
 8)NOTE: PLEASE ALSO NOTE THE CIRCUITING
 THAT IS NOT LABELED DUE TO EXISTING
 CONDITIONS, WILL NEED TO BE REVISED
 BEFORE FINAL.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372