| 2002-09-04 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE CLARIFY "NEW" SERVICE |
| | SHOWN ON RISER DIAGRAM. PLEASE SHOW IF |
| | NEW SERVICE IS COMING FROM THE SAME TRAN |
| | SFORMER OF EXISTING SERVICE IN ORDER TO |
| | MEET THE REQ`MENTS OF 230-2. |
| | PLEASE CLARIFY IF EXISTING ELECTRICAL |
| | ROOM IS ATTACHED STRUCTUALY. PER 225-31 |
| | |
| | 2)NOTE: PLEASE NOTE CIRCUITING SHOWN FOR |
| | A PANEL "312", PLEASE NOTE NO PANEL |
| | 312 SHOWN ON RISER? (MISPRINT?) |
| | |
| | 3)NOTE: PLEASENOTE CIRCUITING FOR |
| | EMERGENCY LIGHTING TO MEET 700-12-E |
| | |
| | 4)NOTE: PLEASE NOTE LOAD CALCULATIONS |
| | NEED TO SHOW TRACK LIGHTING PER 220-12B |
| | ALSO, ALL CONTINUOUS LOADS AND LARGEST |
| | MOTOR AT 125%. 230-42/215-3 ETC. |
| | |
| | 5)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | GFI FOR ROOFTOP EQUIPMENT PER 210-63 |
| | |
| | 6)NOTE: PLEASE NOTE AN EQUIPMENT GROUND |
| | IS BEING SHOWN BEFORE THE FIRST MEANS |
| | OF DISCONNECT AND METER? PLEASE CLARIFY? |
| | THIS WOULD BE PARALLELING THE NEUTRAL. |
| | PLEASE ALSO CLARIFY WHY THE NEUTRAL IS |
| | NOT BEING TAKEN TO THE FIRST MEANS OF |
| | DISC? REQ`D PER 250-24 |
| | |
| | 7)NOTE: PLEASE NOTE THAT INFORMATION |
| | WILL BE REQ`D FOR FIXTURE TYPE "D". |
| | PLEASE NOTE FIXTURE SCHEDULE WILL NEED |
| | TO BE REVISED. |
| | |
| | 8)NOTE: PLEASE ALSO NOTE THE CIRCUITING |
| | THAT IS NOT LABELED DUE TO EXISTING |
| | CONDITIONS, WILL NEED TO BE REVISED |
| | BEFORE FINAL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |