2002-09-04 00:00:00THIS PROPERTY IS SUBJECT TO REVIEW BY
 THE CITY'S HISTORICAL PRESERVATION
 PLANNERCALL 561-659-8031 FOR MORE
 INFORMATION.
  
 THE PROPOSED ELEVATOR IS SUBJECT TO THE
 REQUIREMENTS OF FBC 3003.4.2.
  
 THE CHANGE OF OCCUPANCY USE FROM
 RESIDENTIAL TO OFFICE MAY BE SUBJECT TO
 IMPACT FEES COLLECTED BY PALM BEACH
 COUNTY.BEFORE A PERMIT TO CONSTRUCT
 MAY BE ISSUED, THE PERMIT PLANS MUST BE
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 AN ENGINEER'S ANALYSIS WILL BE NECESSARY
 TO ASCCERTAIN THE EXISTING CONDITIONS
 SUITABILITY FOR THE CHANGED FLOOR
 LOADING REQUIREMENTS.SEE FBC
 3401.2.2.2. AND FBC 1604.1.
  
 SHEET A1 DECLARES TYPE IV CONSTRUCTION.
  
 THE EXISTING BUILDING IS TYPE V 1HR
 PROTECTED.SEE FBC 607.PLEASE REVISE
 AS NECESSARY, SEE ALSO APPENDIX F102.2.5
 OF THE CITY AMENDMENTS TO THE FBC RE:
 ONE HOUR PROTECTION IN TWO STORY
 BUILDINGS.
  
 AS PROVIDED FOR IN FBC 3401.7.2 THE
 EXISTING STAIRS SHOULD BE ENCLOSED IN
 ACCODANCE WITH FBC 1006.1.1 SUBJECT TO
 THE HISTORIC PRESERVATION REQUIREMENTS.
  
 THE EXTERIOR OPENINGS IN THE PLANE OF
 THE EXIT DOOR #201 ARE REQUIRED TO BE
 PROTECTED FOR THE DISTANCE WITHIN 10'
 SEE FBC 1006.2.4.
  
 THE PROPOSED GLAZING IN ROOM #222 MUST
 COMPLY WITH FBC 2405.2.1 #3 & #4.
  
 SHOW HOW THE AREA OF RESCUE ASSISTANCE
 FOR THE HANDICAP WILL BE ACCOMPLISHED.
 SEE FBC 11-4.3.11.