Plan Review Notes
Plan Review Notes For Permit 02081566
Permit Number 02081566
Review Stop B
Sequence Number 1
Notes
Date Text
2002-09-09 00:00:00SHEET ID 01 HARDSCAPE NOTE #50 DECLARES
 120 MPH WIND SPEED.WEST PALM BEACH IS
 IN THE 140 MPH ZONE.PLEASE REVISE AS
 NECESSARY.
  
 SHEET ID 01 NOTE 17 CALLS OUT 1500 PSI
 F'M.SH12 CALLS OUT 2000 PSI F'M.
 PLEASE CLARIFY DESIGN INTENT.
  
 THE POOL SHOWER SHOWN IN SECTION 2/HS09
 IS REQUIRED TO HAVE ACCESSIBLE CONTROLS.
 SEE FBC 11-4.27.
  
 THE HANDRAIL HEIGHT SHOWN IN SECTION
 3/HS10 SHOULD BE MEASURED PERPENDICULAR
 FROM THE LEADING EDGE OF THE TREAD
 NOSING,SEE FBC 1007.5.1.
  
 SECTION 3/HS10 REQUIRES HANDRAILS ON
 EACH SIDE.SEE FBC 1007.5.2 AND FBC
 11-4.9.4.
  
 SH 11 AND SH 12.HOW ARE THE ROOF BEAMS
 CONNECTED TO THE CONCRETE AND MASONRY
 COLUMNS?