2 |
|
| Notes |
| Date |
Text |
| 2003-03-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) LINE TO RANGE (180,000 BTU) IS TOO | | | SMALL @ 178' DEVELOPED LENGTH. EITHER | | | 1-1/4" PIPE IS REQUIRED OR A 2 LB. | | | SYSTEM IS REQUIRED WITH A REGULATOR AT | | | THE UNION PRIOR TO ENTERING THE BLDG. | | | AND AT EACH BBQ AND THE POOL HEATER. | | | IF 2 LB SYSTEM USED, PLEASE PROVIDE CUT | | | SHEETS FOR REGULATORS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|