| Plan Review Notes For Permit 02081480 |
| Permit Number |
02081480 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-13 00:00:00 | | | | | | | | | | ***** ISSUED PERMIT***** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 02081480 | | | ADDRESS: 9271 HERON COVE DR | | | CONT: LENNAR HOMES | | | TELL # (561) 790-0202 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | | | *****PROVISO****** | | | | | | 1) SHEET S-2 REVISE TRUSS ANCHOR SCHED- | | | ULE, INDICATES THE USE OF SEMCO TRUSS | | | ANCHORS, NO LONGER IN BUSINESS, THEIR | | | PRODUCTS ARE OFF THE MARKET. PROVIDE | | | NEW SCHEDULE BEFORE ROOF FRAMING INSPEC- | | | TION. | | | | | | 2) PROVIDE FLOOD ZONE ELEVATION | | | CERTIFICATE FOR NEW CONSTRUTION WITH | | | BASE FLOOD ELEVATION, CITY CODE REQUIRES | | | AN ADDITIONAL 6".LOCATED IN A "AO ZONE" | | | CERTIFICATE REQUIRED BEFORE C.O. | | | | | | 3) DISCREPANCY ENERGY CALS INDICATE THE | | | USE OF R-30 INSULATION ABOVE THE CEILING | | | VS SHEET A-4.1 DETAIL 1 INDICATING R-19 | | | CORRECT! | | | | | | BUILDING PLAN REVIW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|