| Plan Review Notes For Permit 02081382 |
| Permit Number |
02081382 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-07 00:00:00 | PASS/PROVISO | | | 1) REFER TO SECTION 402.3.1 BATHROOM | | | EXHAUST FBC 2001 | | | 2) NEED FRESH AIR CALCULATIONS FOR ROUGH | | | INSPECTION | | | 3) CONDENSATE DRAIN MUST TERMINATE A MIN | | | 12IN.FROM BUILDING 1503.4.4 FBC.2001 | | | 4) NEED PRESSURE TEST ON REF.LINES | | | 150 LB. 1108.1 FBC 2001 | | | THIS PROVISO IS FOR UNITS C,CR,B,BR,CM, | | | AND CMR | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|