Plan Review Notes
Plan Review Notes For Permit 02081382
Permit Number 02081382
Review Stop M
Sequence Number 1
Notes
Date Text
2002-09-07 00:00:00PASS/PROVISO
 1) REFER TO SECTION 402.3.1 BATHROOM
 EXHAUST FBC 2001
 2) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 3) CONDENSATE DRAIN MUST TERMINATE A MIN
 12IN.FROM BUILDING 1503.4.4 FBC.2001
 4) NEED PRESSURE TEST ON REF.LINES
 150 LB. 1108.1 FBC 2001
 THIS PROVISO IS FOR UNITS C,CR,B,BR,CM,
 AND CMR
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390