| 2002-09-11 00:00:00 | *********** NOTES / REDLINED ********* | | | | | | MISSING EQUIPMENT GROUND BETWEEN MAIN | | | DISC AND PANEL. SIZE PER 250-122 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|