| 2002-08-28 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PLEASE NOTE THERE MUST BE A GFI | | | INSTALLED IN THE FRONT OF THE RESIDENCE | | | PER 210-52(E). | | | | | | 2} PLEASE CLARIFY THE #6 GROUND SHOWN | | | BEING RAN WITH THE FPL SERVICE. | | | | | | 3} THE SMOKE DETECTOR IN THE HALLWAY | | | UPSTAIRS IS TO BE LOCATED 5" FROM | | | RETURN AIR(ALSO 3' FROM BATHS, KITCHENS | | | AND AIR DUCTS PER NFPA-72,CHAPTER | | | 8,1999 EDT. | | | | | | PLEASE REVISE PLANS AND RESUBMIT FOR | | | REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|