| Plan Review Notes For Permit 02081323 |
| Permit Number |
02081323 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-28 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THAT THE #6 GROUND BETWEEN | | | THE METER AND THE MAIN DISCONNECT | | | CREATES A PARALLEL PATH TO THE | | | GROUNDING ELECTRODE SYSTEM WITH THE | | | NEUTRAL.ALSO CLARIFY THE #6 GROUND | | | SHOWN BEING RAN WITH FPL SERVICE. | | | | | | THE SMOKE DETECTOR SHOWN IN THE HALLWAY | | | UPSTAIRS IS TO BE LOCATED AT LEAST | | | 5'FROM RETURN AIR DUCTS. | | | | | | REVISE THE PLANS AND RESUBMIT FOR | | | REVIEW. | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|