| Plan Review Notes For Permit 02081144 |
| Permit Number |
02081144 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-10 00:00:00 | *********** NOTE / REVISION ************ | | | | | | PLEASE SEE ITEMS REDLINED ON PLANS, | | | | | | PLEASE NOTE MISSING RECEPTS PER | | | 210-52,210-52-H, 210-52-C-1 | | | | | | PLEASE NOTE MISSING EQIPMENT GROUNDING | | | CONDUCTOR BETWEEN MAIN DISC AND PANEL. | | | SIZE PER 250-122 | | | | | | PLEASE NOTE: ALL OPTIONS SHOWN ON PLANS | | | THAT ARE INSTALLED, NEED TO BE RE-DRAWN | | | AS PERMANENT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|