| 2002-09-09 00:00:00 | ************ NOTES REDLINED ******* | | | | | | PLEASE NOTE THAT ANY OPTIONS SHOWN ON | | | PLANS AND THAT ARE INSTALLED NEED TO | | | BE REVISED BEFORE ROUGH ELECTRICAL | | | INSPECTION. | | | | | | PLEASE ALSO NOTE THERE ARE ITEMS RED- | | | -LINED ON PLANS. | | | | | | 1)NOTE : PLEASE NOTE MISSING OUTLETS PER | | | 210-52 IN MANY LOCATIONS. | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLETS | | | KITCHEN COUNTERSPACEPER 210-52-C-1 | | | | | | 3)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND PANEL. SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|