2002-09-09 00:00:00************ NOTES REDLINED *******
  
 PLEASE NOTE THAT ANY OPTIONS SHOWN ON
 PLANS AND THAT ARE INSTALLED NEED TO
 BE REVISED BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 PLEASE ALSO NOTE THERE ARE ITEMS RED-
 -LINED ON PLANS.
  
 1)NOTE : PLEASE NOTE MISSING OUTLETS PER
 210-52 IN MANY LOCATIONS.
  
 2)NOTE: PLEASE NOTE MISSING OUTLETS
 KITCHEN COUNTERSPACEPER 210-52-C-1
  
 3)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW