| 2002-08-22 00:00:00 | ************* UNSAT ****************** |
| | |
| | 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | PLEASE NOTE MISSING REQ`D RECEPTS IN |
| | MANY BATHS REQ`D PER 210-52D |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 4)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| | KITCHEN OUTLETS TO MEET 210-52-C,1,2,3, |
| | ,4,5. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING EGRESS |
| | LIGHTING PER 210-70, HALLWAY ETC. |
| | |
| | 6) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 7))NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 8)NOTE: PLEASE SHOW LOCATION OF EXISTING |
| | PANELS. |
| | PLEASE SUBMIT PANEL SCHEDULES. |
| | |
| | PLEASE NOTE THAT NO HANDWRITTEN CHANGES |
| | MAY BE ON PLANS, UNLESS EACH CHANGE IS |
| | SIGNED AND DATED BY THE ARCH OF RECORD. |
| | FS/FAC 481.221. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |