2002-10-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) INDICATE THE INTERNAL PRESSURE
 COEFFICIENT ON THE PLANS PER 2001 FBC
 1606.1.7. FOR AN ENCLOSED STRUCTURE IT
 IS +/- .18.
  
 2) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BBQ ON
 THE COVERED PORCH AT REAR.
  
 3) THE PRODUCT APPROVAL FOR THE SERIES
 PW-701 FIXED WINDOWS IS MISSING PAGE 8
 OF 8 FROM THE APPROVED DRAWINGS #4231.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE OVAL FIXED GLASS
 WINDOWS. THESE WERE NOT SHOWN ON THE
 PW-701 PRODUCT APPROVAL.
  
 5) THE DESIGNER OF RECORD (ARCHITECT) IS
 REQUIRED TO INITIAL AND DATE EACH OF THE
 REVISIONS THAT WERE RED LINED ON THE
 ORIGINAL PLANS.
  